Calculator

4to20.com Industrial Signal Calculators & Diagnostics
Process Value
1000.00 PSI
Current
12.00 mA
Raw Value
16000

Auto-populated from the ranges set in the Scaling Calculator tab.

Span %CurrentProcess ValueRaw Value
Sensor Wire Break / Open Loop< 3.6 mA
Under-Range Signal3.6 – 4.0 mA
Normal Measurement Span4.0 – 20.0 mA
Over-Range Signal20.0 – 20.5 mA
Sensor Short / High Saturation> 21.0 mA
Normal Measurement Span
Max Allowable Resistance
600.0 Ω
Actual Loop Resistance
280.0 Ω
Headroom
320.0 Ω
Loop OK — within supply capability

Rmax = (Vsupply − Vtx min) / 0.020 A. If actual resistance (wire + load) exceeds Rmax, the transmitter cannot be guaranteed to drive a full 20 mA signal.